Honeywell Fire Systems has identified an issue that could affect the normal operation of BG-10 series pull stations manufactured from 1992 through 2010. The majority were manufactured from 1992 through 2000. These pull stations were distributed under multiple brands including ADT, Fire-Lite Alarms, Johnson Control Inc. and NOTIFIER.
What is the Issue?
  Over time, the seal installed around the alarm switch could deteriorate, preventing the switch from signaling an alarm when the pull station is activated. While annual testing required by NFPA 72 will help identify abnormal pull station operation, Honeywell Fire Systems wants to raise awareness and help users determine the best immediate course of action in a timely fashion. Download Pull Station Issue Description Notice (PDF)
Is my BG-10 Affected?
  Read information on affected models and recommended replacement devices
How to Inspect and Replace BG-10 Series Seals
  Download step-by-step instructions (PDF)
Order Replacement Seals
  Complete the online order form
 

 Watch the Video: How to Inspect and Replace BG-10 Series Seals